How the checker calculates
Galvanized piles corrode in two stages. First the zinc is consumed, at a rate set mainly by soil resistivity. Then bare carbon steel corrodes from both faces of the web. The checker estimates when the zinc runs out, how many years of bare-steel loss fall inside the design life, and how much web is left at the end.
| Soil resistivity | Class | Zinc loss | µm/yr |
|---|---|---|---|
| > 10,000 ohm-cm | Mild / non-corrosive | 0.08–0.16 mils/yr | 2–4 |
| 5,000–10,000 ohm-cm | Mild–moderate | 0.16–0.31 mils/yr | 4–8 |
| 2,000–5,000 ohm-cm | Moderate | 0.31–0.47 mils/yr | 8–12 |
| < 2,000 ohm-cm | Aggressive / corrosive | 0.47–0.85+ mils/yr | 12–22+ |
Multipliers
- pH: +35% per pH unit below 5.5, +40% per unit above 10.
- Chlorides: up to +80% at 2,000 ppm.
- Sulfates: up to +50% at 3,000 ppm.
- Moisture: ×0.85 well-drained, ×1.0 seasonal, ×1.3 saturated.
Coatings and bare steel
ASTM A123 requires a minimum average of 3.9–4.7 mils on structural shapes; 4.3 mils is used as the typical average. Reactive silicon/phosphorus steel can reach 5.5–7.5+ mils (6.0 used). Pre-galvanized G235 sheet carries about 2.0 mils per side. Zn-Al-Mg coatings are modelled at 40% of the zinc loss rate. The soil-air collar option cuts zinc and steel loss at the grade line, where corrosion usually governs. Bare carbon steel loses about 0.35–1.9 mils per year per side across the resistivity range, scaled by the same multipliers.
Verdict thresholds
Pass: at least 85% of the original web remains at end of design life. Marginal: 70–85%. High risk: below 70%. Structural adequacy depends on the section modulus actually required by the racking loads, so treat these as screening flags for the engineer of record, not a design check.
Section properties for every profile are on driven W-beam piles. For C-piles versus W-beams in corrosive ground, see roll-formed C-piles.